Rockwell Automation 1786-RPFM ControlNet Modular Repeater Med-distance Fiber Module Installation Instructio User Manual

Page 14

Advertising
background image

14 ControlNet Modular Repeater Medium-distance Fiber Module

Rockwell Automation Publication 1786-IN011C-EN-P - November 2010

Environmental Specifications - 1786-RPFM

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp
Heat)

5...95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating)

5 g @ 10...500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Advertising