Install the module, Connect the input cord sets to the lp2 module – Rockwell Automation 1792D-4B0LP INSTL INSTR ARMORBLOCK INPUT User Manual

Page 3

Advertising
background image

ArmorBlock LP2 4 Sinking Input Module

3

Publication 1792D-5.27- January 1999

Install the Module

1.

Attach the module using the dimensions shown below.

2.

Connect the grey DeviceNet cable to the DeviceNet trunk. Use the
1485P-P1R5-MN5R1 T-Part tap to make the connection to round
media. Use the 1485P-P1E4-R5 to connect to the Kwik Link flat media
system.

Connect the Input Cord Sets to the LP2 Module

This module uses 5 pin micro (12mm) style PCB mounted connectors.

Four micro caps cover the connectors on your module. Remove the caps
and connect your cables to the appropriate ports.

Use the micro caps to cover and seal unused ports. A Pinout diagram for
the connector is shown next.

I0

I1

I2

I3

Network Status

Module Status

4.21 in

107mm

0.25 in

6.25mm

12in

305mm

1.95 in

49.5mm

1.02 in

26.0mm

1

5

3

4

2

Input Micro-Connector

(View into Sockets)

Pin 1 Sensor Source Voltage
Pin 2 Not Used

Pin 3 Return Logic Ground

1

Pin 4 Input A
Pin 5 Not Used

1

Logic Ground is approximately 0.4V above DeviceNet V-measured at the module.

Advertising