Specifications – Rockwell Automation 1762-OB16 Solid State 24V dc Source Output Module User Manual

Page 11

Advertising
background image

Solid State 24V DC Source Output Module 11

Publication 1762-IN011B-EN-P - June 2013

Specifications

General Specifications

Specification

Value

Dimensions, HxWxD

90 x 40.4 x 87 mm (height including mounting tabs is 110 mm)

3.54 x 1.59 x 3.43 in. (height including mounting tabs is 4.33 in.)

Approximate Shipping Weight

(with carton)

235 g (0.52 lbs.)

Temperature, nonoperating

-40…85 °C (-40…185 °F)

Temperature, operating

0…55 °C (32…131 °F)

Humidity, operating

5…95% non-condensing

Altitude, operating

2000 m (6561 ft)

Vibration, operating

10…500 Hz, 5 g, 0.030 in. max. peak-to-peak, 2 hours per axis

Shock

Operating: 30 g panel mounted, 3 pulses per axis

Non-Operating: 50 g panel mounted, 3 pulses per axis

(40 g DIN Rail mounted)

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D

ISA/ANSI 12.12.01

(C-UL under CSA C22.2 No. 213)

Radiated and Conducted Emissions

EN50081-2 Class A

ESD Immunity (IEC1000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity (IEC1000-4-3)

10 V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz
keyed carrier

Fast Transient Burst (IEC1000-4-4)

2 kV, 5 kHz

Surge Immunity (IEC1000-4-5)

2 kV common mode, 1 kV differential mode

Conducted Immunity (IEC1000-4-6)

10V, 0.15…80 MHz

(1)

(1) Conducted Immunity frequency range may be 150 kHz…30 MHz if the Radiated Immunity frequency range is

30…1000 MHz.