North american hazardous location approval, Warning – Rockwell Automation 1762-OB16 Solid State 24V dc Source Output Module User Manual
Page 14
 
14 Solid State 24V DC Source Output Module
Publication 1762-IN011B-EN-P - June 2013
North American Hazardous Location Approval
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous 
locations only.
The following WARNING statement applies to use in hazardous locations.
The following information applies when 
operating this equipment in hazardous 
locations:
Informations sur l’utilisation de cet équipement 
en environnements dangereux:
Products marked "CL I, DIV 2, GP A, B, C, D" are 
suitable for use in Class I Division 2 Groups A, B, C, D, 
Hazardous Locations and nonhazardous locations only. 
Each product is supplied with markings on the rating 
nameplate indicating the hazardous location 
temperature code. When combining products within a 
system, the most adverse temperature code (lowest 
"T" number) may be used to help determine the overall 
temperature code of the system. Combinations of 
equipment in your system are subject to investigation 
by the local Authority Having Jurisdiction at the time 
of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne 
conviennent qu'à une utilisation en environnements de 
Classe I Division 2 Groupes A, B, C, D dangereux et non 
dangereux. Chaque produit est livré avec des 
marquages sur sa plaque d'identification qui indiquent 
le code de température pour les environnements 
dangereux. Lorsque plusieurs produits sont combinés 
dans un système, le code de température le plus 
défavorable (code de température le plus faible) peut 
être utilisé pour déterminer le code de température 
global du système. Les combinaisons d'équipements 
dans le système sont sujettes à inspection par les 
autorités locales qualifiées au moment de 
l'installation.
WARNING
EXPLOSION HAZARD
• Substitution of components may impair
suitability for Class I, Division 2.
• Do not replace components or disconnect
equipment unless power has been 
switched off.
• Do not connect or disconnect components
unless power has been switched off.
• This product must be installed in an
enclosure.
• In Class I, Division 2 applications, the bus
connector must be fully seated and the 
bus connector cover must be snapped in 
place.
• In Class I, Division 2 applications, all
modules must be mounted in direct 
contact with each other as shown on 
Page 6. If DIN rail mounting is used, an 
end stop must be installed ahead of the 
controller and after the last 1762 I/O 
module.
• All wiring must comply with N.E.C. article
501-4(b).
• The interior of the enclosure must be
accessible only by the use of a tool.
• For applicable equipment (relay modules,
etc.), exposure to some chemicals may 
degrade the sealing properties of 
materials used in the following devices: 
Relays, Epoxy. It is recommended that the 
User periodically inspect these devices for 
any degradation of properties and replace 
the module if degradation is found.
AVERTISSEMENT
RISQUE D’EXPLOSION
• La substitution de composants peut rendre
cet équipement impropre à une utilisation 
en environnement de Classe 1, Division 2. 
• Ne pas remplacer de composants ou
déconnecter l'équipement sans s'être 
assuré que l'alimentation est coupée. 
• Ne pas connecter ou déconnecter des
composants sans s'être assuré que 
l'alimentation est coupée. 
• Ce produit doit être installé dans une
armoire.
• Pour les applications de Classe I, Division 2,
le connecteur de bus doit être correctement 
installé et son couvercle enclenché. 
• Pour les applications de Classe 1, Division
2, tous les modules doivent être installés en 
contact direct les uns avec les autres, 
comme indiqué page 6. Si on utilise le 
montage sur rail DIN, une butée doit être 
placée à l'avant de l'automate et après la 
dernière unité d'E/S 1762.