Troubleshoot with the indicators – Rockwell Automation 1790D-XXXX DeviceNet Analog Base Terminal Block CompactBlock LDX I/O User Manual

Page 12

Advertising
background image

12

Publication 1790-IN002B-EN-P - April 2003

1790D-TN0C2, -TN0V2 Output Data File

Word/Bit Descriptions for 1790D-TN0C2, -TN0V2 Analog Output Module

Troubleshoot with the Indicators

The 1790D I/O block has the following indicators:

• module status
• network status
• I/O status

Wor
d

Bit Position

1
5

1
4

1
3

1
2

1
1

1
0

9

8

7

6

5

4

3

2

1

0

0

Not Used

Analog Output Data Channel 0

1

Not Used

Analog Output Data Channel 1

Word

Decimal Bit

Description

Write Word
0

Bits 00-11

Channel 0 output data

Bits 12-15

Not used: Set to 0

Write Word
1

Bits 00-11

Channel 1 output data

Bits 12-15

Not used: Set to 0

Mod/Net Status Indicator

LED Indicator:

Status:

Description:

Module Status

Solid Red

Unrecoverable fault in base unit

Flashing Red

Recoverable fault

Solid Green

Normal operation - OK

Flashing Green

Standby

Off

No power

LED Indicator:

Status:

Description:

Network Status

Solid Red

Unrecoverable communication fault

Flashing Red

Recoverable communication fault

Solid Green

Communication path complete - OK

Flashing Green

Communication path incomplete

Off

Device not online or not powered