Rockwell Automation 1790D-XXXX DeviceNet Analog Base Terminal Block CompactBlock LDX I/O User Manual
Page 14
 
14
Publication 1790-IN002B-EN-P - April 2003
DeviceNet Analog Base Terminal Block Specifications
The following table contains specifications that are common to 
all of the blocks in this document. Individual base block 
specifications are detailed after this table.
I/O Channel LED Status Indicator
1790D-TN0V2
1790D-TN0C2
Status:
Description:
Status:
Description:
Flashing Green/
Red 
Power up
Flashing Green/
Red 
Power up
Off
Off line
Off
Off line
Off
On line and no field 
power
Off
On line and no field 
power
Green
DeviceNet 
connection and no 
field power
Green
DeviceNet 
connection and no 
field power
Green
Field power and 
open wire
Green
Field power and 
open wire
Green
Field power and valid 
output
Green
Field power and valid 
output
Flashing Red
Field power and 
output out of range
Flashing Red
Field power and 
output out of range
Flashing Green
Output idle
Flashing Green
Output idle
Flashing Red
Recoverable fault
Flashing Red
Recoverable fault
Environmental Specifications
Operating Temperature
0 to 55°C (32 to 131°F)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Storage Temperature
-40 to 85°C (-40 to 185°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal 
Shock)
Relative Humidity
5-90% non-condensing
IEC 60068-2-30 (Test Db, Un-packaged Non-operating)
Operating Altitude
2000m
Specifications continued on next page.