Rockwell Automation 1790D-XXXX DeviceNet Analog Base Terminal Block CompactBlock LDX I/O User Manual

Page 14

Advertising
background image

14

Publication 1790-IN002B-EN-P - April 2003

DeviceNet Analog Base Terminal Block Specifications

The following table contains specifications that are common to
all of the blocks in this document. Individual base block
specifications are detailed after this table.

I/O Channel LED Status Indicator

1790D-TN0V2

1790D-TN0C2

Status:

Description:

Status:

Description:

Flashing Green/
Red

Power up

Flashing Green/
Red

Power up

Off

Off line

Off

Off line

Off

On line and no field
power

Off

On line and no field
power

Green

DeviceNet
connection and no
field power

Green

DeviceNet
connection and no
field power

Green

Field power and
open wire

Green

Field power and
open wire

Green

Field power and valid
output

Green

Field power and valid
output

Flashing Red

Field power and
output out of range

Flashing Red

Field power and
output out of range

Flashing Green

Output idle

Flashing Green

Output idle

Flashing Red

Recoverable fault

Flashing Red

Recoverable fault

Environmental Specifications

Operating Temperature

0 to 55°C (32 to 131°F)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

Storage Temperature

-40 to 85°C (-40 to 185°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock)

Relative Humidity

5-90% non-condensing
IEC 60068-2-30 (Test Db, Un-packaged Non-operating)

Operating Altitude

2000m

Specifications continued on next page.