Mount the optional expansion blocks, Wire the terminal blocks, Pull – Rockwell Automation 1790D-XXXX DeviceNet Analog Base Terminal Block CompactBlock LDX I/O User Manual

Page 8

Advertising
background image

8

Publication 1790-IN002B-EN-P - April 2003

Mount the Optional Expansion Blocks

Mount the expansion block by connecting it to a
previously-installed CompactBlock LDX I/O base or expansion
block.

Beginning with the base block, you can mount your
expansion blocks either horizontally or vertically:

• horizontally (left to right) - add expansion blocks in an

end-to-end configuration

• vertically (up or down) - add expansion blocks either up or

down in a back-to-back configuration. In this configuration,
you must use the optional 15cm ribbon cable
(1790-15CMCBL) and alternately position the blocks in a
right-side up, upside-down fashion.

You can mount your blocks on a panel or DIN rail as
described in the previous section.

Wire the Terminal Blocks

The following figures show how to wire the terminal blocks.

EXPANSION UNIT

Compact

Compact

Block LDX

PULL

PULL

PULL

PULL

RIGHT SIDE UP

EXPANSION UNIT

Compact

Compact

Block LDX

PULL

PULL

PULL

PULL

RIGHT SIDE UP

EXPANSION UNIT

Compact

Compact

Block LDX

PULL

PULL

PULL

PULL

RIGHT SIDE UP

EXPANSION UNIT

Compact

Compact

Block LDX

PULL

PULL

PULL

PULL

RIGHT SIDE UP

EXPANSION UNIT

Compact

Compact

Block LDX

PULL

PULL

PULL

PULL

RIGHT SIDE UP

EXPANSION UNIT

Compact

Compact

Block LDX

PULL

PULL

PULL

PULL

UPSIDE DOWN

EXPANSION UNIT

Compact

Compact

Block LDX

PULL

PULL

PULL

PULL

RIGHT SIDE UP

The longer expansion cable
(1790-15CMCBL) will allow
up to 7cm of space in between
blocks.

Horizontal mounting

Vertical mounting