18 point i/o devicenet adapter publication – Rockwell Automation 1734-ADN, ADNX Point I/O DeviceNet Adapter Installation Instructions User Manual
Page 18
 
18 POINT I/O DeviceNet Adapter
Publication
1734-IN026A-EN-P - April 2005
1
Maxi(mum) Backplane MAC ID is an attribute for 1734-ADNX only. This value represents the highest
node address of a module residing on the backplane. The value must be greater than or equal to the 
right-most backplane Subnet module, but less than that of any non-backplane Subnet module. 
Indicator
Indication
Probable Cause
Take This Action
Subnet and 
PointBus 
Status
Off
Device is not online.
- Device has not completed 
Dup_MAC_ID test.
- Device is not powered. - Check 
module status indicator.
Check adapter status 
indicator to determine if you 
need more time to complete 
the dup_MAC_id test or if 
you need to power the 
adapter. 
Flashing 
Green
Device is online but has no 
connections in the established 
state.
None
Green
Device is online and has 
connections in the established 
state.
None
Flashing Red
No scanlist is available.
I/O module is missing.
Max backplane MAC ID is not 
set right (1734-ADNX).
Make sure all I/O modules 
are connected and using the 
correct MAC IDs.
Check “Cycling Node 
Status” parameter in 
RSNetWorx for DeviceNet.
For 1734-ADNX, terminate 
the 1734-ADNX Subnet and 
correctly set the Max 
Backplane MAC ID.
1
Red
Critical link failure - 
communication device failed. 
Device detected error that 
prevents it from communicating 
on the network.
Make sure an I/O module is 
not using a MAC ID =0.
Make sure all backplane 
modules are communicating 
at the proper baudrate.