Communications Interface Specifications (continued)
Expansion I/O Capacity
Up to 13 modules (13 times 75mA = 0.975, just under the
limit of 1.0A), based on POINTBus current requirements
The actual number of modules can vary. Add up the current
requirements of the modules you want to use to make sure
they do not exceed the amperage limit of the adapter. Total
expansion is up to 63 modules - 13 modules maximum with
the adapter. Add 1734-EP24DC modules for an additional
17 modules (or less based on current requirements), up to
63 modules maximum.
Cat. No.
PointBus Current Requirements
1734-IB2
75mA
1734-IB4
75mA
1734-IB8
75mA
1734-IV2
75mA
1734-IV4
75mA
1734-OB2
75mA
1734-OB4
75mA
1734-OB8
75mA
1734-OB2E
75mA
1734-OB2EP
75mA
1734-OB4E
75mA
1734-OB8E
75mA
1734-OV2E
75mA
1734-OV4E
75mA
1734-OW2
80mA
1734-OX2
100mA
1734-IE2C
75mA
1734-OE2C
75mA
1734-IE2V
75mA
1734-OE2V
75mA
1734-IA2
75mA
1734-IM2
75mA
1734-OA2
75mA
1734-IJ2
160mA
1734-IK2
160mA
1734-IR2
220mA
1734-IT2I
175mA
1734-SSI
110mA
1734-VHSC5
180mA
1734-VHSC24
180mA
1734-232ASC
75mA