4 POINT I/O DeviceNet Adapter
Publication
1734-IN026A-EN-P - April 2005
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution 
Degree 2 industrial environment, in overvoltage 
Category II applications (as defined in IEC 
publication 60664-1), at altitudes up to 2000 meters 
without derating.
This equipment is considered Group 1, Class A 
industrial equipment according to IEC/CISPR 
Publication 11. Without appropriate precautions, 
there may be potential difficulties ensuring 
electromagnetic compatibility in other environments 
due to conducted as well as radiated disturbance.
This equipment is supplied as “open type” 
equipment. It must be mounted within an enclosure 
that is suitably designed for those specific 
environmental conditions that will be present and 
appropriately designed to prevent personal injury 
resulting from accessibility to live parts. The interior 
of the enclosure must be accessible only by the use 
of a tool. Subsequent sections of this publication 
may contain additional information regarding 
specific enclosure type ratings that are required to 
comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC 
publication 60529, as applicable, for explanations of 
the degrees of protection provided by different 
types of enclosure. Also, see the appropriate 
sections in this publication, as well as the 
Allen-Bradley publication 1770-4.1 (“Industrial 
Automation Wiring and Grounding Guidelines”), for 
additional installation requirements pertaining to 
this equipment.