Checking the rs-232 module diagnostics, Checking the rsć232 module diagnostics, Module status indicator – Rockwell Automation 1771-SDN/B INSTL.INSTR.DEVICENET SEMINAR User Manual

Page 19: Network status indicator, Rsć232 status indicator

Advertising
background image

DeviceNet Seminar Installation Instructions

19

Publication 1787Ć5.5 - December 1995

The three status indicators on the RS-232 module give you
information about your network and its connections. Conditions for
this lab should be as indicated in the shaded areas of the
following tables.

Module Status Indicator

If the indicator is

Then

Which indicates

Take this action

Off

There is no power being supplied to

the module.

There is no power. Apply power to the module.

Solid green

The module is operating normally.

The module is onĆ

line and a commuĆ

nication rate

is detected.

Do nothing.

Blinking green

The module is operating normally

awaiting for initialization from

the host.

The module is in

autobaud mode.

Initialize the module.

Solid red

There is an unrecoverable fault in

the module.

The module has a

critical fault.

Replace the module.

Blinking red

There is a recoverable fault in

the module.

The module has a

recoverable fault.

Reconfigure, reset, and perĆ

form the error recovery steps

to the module.

Network Status Indicator

If the indicator is

Then

Which indicates

Take this action

Off

The module is offline.

The DeviceNet

network is offline.

Go online.

Solid green

The module is online and communiĆ

cating over the DeviceNet network.

The DeviceNet

network is online.

Do nothing.

Blinking green

The module is online.

The DeviceNet

network is online

but not communiĆ

cating.

Do nothing.

Solid red

The link between the module and

the DeviceNet network has failed.

There is a critical

error in the

DeviceNet link.

Check your node addresses

and network configurations for

an error.

RSĆ232 Status Indicator

If the indicator is

Then

Which indicates

Take this action

Off

There is no activity and the

DeviceNet link is OK.

There is no comĆ

munication over the

DeviceNet network.

Do nothing.

Blinking green

There is activity and the DeviceNet

link is OK.

Data is being transĆ

mitted or received

by the module.

Do nothing.

Solid red

There is a critical fault in

the module.

The device is

incapable of comĆ

municating on the

DeviceNet network.

Attempt to go online again.

Blinking red

There is a recoverable fault in

the module.

The module has

detected a

nonĆcritical fault.

Check your communication

rate and parity.

Checking the RSĆ232

Module Diagnostics