DeviceNet Seminar Installation Instructions

23

Publication 1787Ć5.5 - December 1995

The DeviceNet channel has a bicolor (green/red) network status
indicator (NET). The following table provides troubleshooting
information about the DeviceNet channel communication link.

If the NET indicator is Then

Which indicates

Take this action

Off

The device has no power or the channel

is disabled for communication due to bus

off condition, loss of network power, or

has been intentionally disabled.

The channel is disabled for DeviceĆ

Net communication.

PowerĆup the module, provide netĆ

work power to channel, and be sure

channel is enabled in both the modĆ

ule configuration table and module

command word.

Flashing Green

The twoĆdigit numeric display for the

channel indicates an error code that proĆ

vides more information about the condiĆ

tion of the channel.

The channel is enabled but no comĆ

munication is occurring.

Configure scan list table for channel

to add devices.

Solid Green

There's normal operation.

All slave devices in the scan list

table are communicating normally

with the module.

Do nothing.

Solid Red

The communications channel has failed.

The two digit numeric display for the

channel displays an error code that proĆ

vides more information about the condiĆ

tion of the channel.

The module may be defective.

Reset module. If failures continue,

replace module.

Flashing Red

The twoĆdigit numeric display for the

channel displays an error code that proĆ

vides more information about the condiĆ

tion of the channel.

At least one of the slave devices in

the module's scan list table has

failed to communicate with the modĆ

ule.

Examine the failed device and the

scan list table for accuracy.

Your 1747-SDN Scanner Module uses numeric displays to indicate
diagnostic information about the status of your module. The display
flashes at 1 second intervals. The following table summarizes the
meanings of the numeric codes.

If the numeric code is Which indicates

Take this action

0 Ć 63

Normal operation. The numeric display

matches the scanner's node address on

the DeviceNet network.

Do nothing.

70

Module failed the Duplicate Node

Address check

Change the module channel address to

another available one. The node address

you selected is already in use on

that channel.

71

Illegal data in scan list table (node numĆ

ber alternately flashes).

Reconfigure the scan list table and

remove any illegal data.

72

Slave device stopped communicating

(node number alternately flashes).

Inspect the field devices and verify

the connections.

73

Device ID does not match scan list table

entry (node number alternately flashes).

Enter a matching scan list device ID.

74

Data overrun on port detected.

Modify your configuration and check for

invalid data.

75

No network traffic has been detected.

Verify your connections.

76

No direct network traffic for the

module detected.

None. The module hears other network

communication.

77

Data size returned does not match scan

lists entry (node number alternately

flashes).

Reconfigure your module and change

the addressing.

78

Slave device in scan list table does not

exist (node number alternately flashes).

Add the device to the network or delete

the scan list entry for that device.

top part of module

DeviceNet

STATUS

MODULE NET

ADDRESS/ERROR

node address

and status

display