Using the Channel 0 Default Communication Push Button

The Channel 0 default communication push
button is located on the front of the controller
in the lower right corner as shown in the
illustration. Use the Channel 0 default
communication push button to change from
the user-defined communication
configuration to the default Communication
mode. The Channel 0 default communication
(DCH0) status indicator turns on (green,
steady) to indicate that the default
communication configuration is active.

Duplicate Packet (Message) Detect

Enabled

ACK Timeout

50 (x 20 ms)

NAK Receive Limit

3 Retries

ENQ Transmit Limit

3 Retries

Data Bits

8

Stop Bits

1

IMPORTANT

Only Channel 0 has a default communication push button.

IMPORTANT

The default communication push button is recessed.
Before pressing the default communication push button, be sure to note the
present communication configuration for Channel 0. Pushing the default
communication push button resets all configured parameters back to their
default settings.
To return the channel to its user-configured parameters, you must enter
them manually while online with the controller or download them as part of
an RSLogix 5000 software project file. To do this online with RSLogix 5000
software, access the Controller Properties dialog box and enter parameters
on the Serial Port, System Protocol, and User Protocol tabs.