1769-L31 CompactLogix Controller 25

Publication

1769-IN069C-EN-P - May 2008

Controller Status Indicators

Indicator

Status

Description

RUN

Off

The controller is in Program or Test mode.

Solid green

The controller is in RUN mode.

FORCE

Off

No tags contain I/O force values.
I/O forces are inactive (disabled).

Solid amber

I/O forces are active (enabled).
I/O force values may or may not exist.

Flashing amber

One or more input or output addresses have been forced to an On
or Off state, but the forces have not been enabled.

BAT

Off

The battery supports memory.

Solid red

Either the battery is:

 not installed.

 95% discharged and should be replaced.

I/O

Off

Either:

 there are no devices in the I/O configuration of the controller.

 the controller does not contain a project (controller memory is

empty).

Solid green

The controller is communicating with all the devices in its I/O
configuration.

Flashing green

One or more devices in the I/O configuration of the controller are
not responding.

Flashing red

The controller is not communicating to any devices.
The controller is faulted.