Before you begin – Rockwell Automation 1769-L31 CompactLogix Controller Installation Instructions User Manual

Page 6

Advertising
background image

6 1769-L31 CompactLogix Controller

Publication

1769-IN069C-EN-P - May 2008

Before You Begin

Use this document as a guide for installing the controller.
Consider the following when planning your CompactLogix system:

 The CompactLogix controller is always the leftmost module in the

system.

 The controller must be located within four modules of the system

power supply. Some I/O modules may be located up to eight modules
away from the power supply. See the documentation for your 1769
I/O modules for details.

 The 1769-L31 controller supports as many as 16 I/O modules in a

maximum of 3 I/O banks with 2 expansion cables.

 Each I/O bank requires its own power supply.
 Only one controller can be used in a CompactLogix system.
 A 1769-ECR right end cap or 1769-ECL left end cap is required to

terminate the end of the communication bus.

These components ship with the controller.

Component

Description

You can also use these components with the controller:

 1756-CP3 or 1747-CP3 serial cable to connect a device to the

RS-232 port

 1784-CF64 or 1784-CF128 industrial CompactFlash card to add

nonvolatile memory

IMPORTANT

The 1769-BA battery is the only battery you can use with the 1769-L31 controller.

1769-BA battery

1747-KY controller key