4 Redundant EtherNet/IP to FOUNDATION Fieldbus Linking Device

Publication 1788-QS006A-EN-P - October 2012

Use BOOTP to Set the IP Address

1. Set the Ethernet switches to 888 (factory default).
2. Apply power to the linking device.
3. Set the IP address by using any BOOTP server.
4. Once the new IP address has been set, power down the linking device.
5. Return the switches to 000.
6. Apply power to the linking device.

Use Switches to Set the IP Address

To set the IP address of the linking device to the 192.168.1.xxx sub net, set the switches to the
required last three digits.

Add a 1788-EN2FFR Module in RSLogix 5000 Software

The module must be added to the RSLogix 5000 I/O tree by selecting the 1788-EN2FFR
module (under a Rockwell Automation Ethernet bridge, for example EN2T).

1. Right-click the Ethernet bridge and choose New Module.

2. Expand the Hiprom Technologies option and select 1788-EN2FFR.

The Module Properties dialog box appears.

3. Type the module's Name, Description, IP Address, and RPI.
4. Click OK.