10 FLEX I/O 8 Output HART Analog Module
Publication
1794-IN109D-EN-P - January 2014
4. Connect -V to terminal 35 on the 34 to 51 row (C).
5. If continuing power to the next terminal base unit, connect a jumper
from terminal 50 (+V) on this base unit to terminal 34 on the next
base unit.
If continuing common to the next terminal base unit, connect a
jumper from terminal 51 (-V) on this base unit to terminal 35 on the
next base unit.
ATTENTION
The 1794-OE8H module shall be used only with Listed Allen-Bradley (Rockwell
Automation) Power Supply (catalog number 1794-PS13) or Listed Class 2 source.
ATTENTION
To reduce susceptibility to noise, power analog modules and digital modules
from separate power supplies.
Wire Connections
Output
Output +
Output -
Output
Output +
Output -
Output 0
A-0
A-1
Output 4
B-17
B-18
Output 1
A-4
A-5
Output 5
B-21
B-22
Output 2
A-8
A-9
Output 6
B-25
B-26
Output 3
A-12
A-13
Output 7
B-29
B-30
+V
Terminals 34 and 50
-V
Terminals 35 and 51
Terminals B-16, B-33, C-38, C-40, C-41, C-43, C-43, C-44, C-45 and C-48 are connected to
chassis ground