Rockwell Automation 1794-OE8H, Series B Flex I/O Output HART Module Installation Instructions User Manual
Page 17

FLEX I/O 8 Output HART Analog Module 17
Publication
1794-IN109D-EN-P - January 2014
HART Input Data
Word
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Reserved
Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0
(HART Communications Status)
1
Reserved
2
Ch0 HART Field Device Status
Ch0 HART Comm Status
3
Reserved
Ch0 HART Loop Status
4
Ch0 HART Primary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
5
6
Ch0 HART Secondary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
7
8
Ch0 HART Tertiary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
9
10
Ch0 HART Fourth (Quaternary) Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
11
12
Ch0 Secondary Value Units Code
Ch0 Primary Value Units Code
13
Ch0 Fourth Value Units Code
Ch0 Tertiary Value Units Code
14
Ch1 HART Field Device Status
Ch1 HART Communication Status
15
Reserved
Ch1 HART Loop Status
16
Ch1 HART Primary Value
17
18
Ch1 HART Secondary Value
19
20
Ch1 HART Teritiary Value
21
22
Ch1 HART Fourth Value
23
24
Ch1 HART Secondary Value Units Code
Ch1 HART Primary Value Units Code
25
Ch1 HART Fourth Value
Ch1 HART Tertiary Value Units Code
26
Ch2 HART Field Device Status
Ch2 HART Communication Status
27
Reserved
Ch2 HART Loop Status