Specifications – Rockwell Automation 1792D-16BT0LP INSTL INSTR ARMORBLOCK LP2 16 User Manual

Page 7

Advertising
background image

7

ArmorBlock LP2 16 Sinking Input Module

Publication 1792D-5.29 - January 1999

Specifications

Network Status Indicator

Indication

Status

None

Not On-line

Green
Blinking
Solid

On-line/No Connections
On-line/Connected

Red
Blink
Solid

Connection Timed Out
Failed Communication: A duplicate
node address exists or the module is at
the wrong baud rate.

I/O Status Indicators

Function

Module Status Indicator

Point Indicator

Condition

Inputs

Green
Green

None
Yellow

No valid input
Valid input

16 Input Module - Cat. No. 1792D-16BT0LP

Sinking Input Specifications

Max

Min

Inputs per block

16 - 3 wire or dry contact PNP devices or 8 - 4 wire
PNP devices

Sensor Source Current (per input)

50mA per point

Off-Wire Sense Current

0.5mA

-

On-state Voltage

25V dc

10V dc

On-state Current

10mA

2mA

Off-state Voltage

5V dc

Off-state Current

1.5mA

General Specifications

Indicators

Network Status - red/green
Module Status - red/green
Point LED - yellow

Communication Rate

• 125Kbps @ 500 meters(1600 feet) for thick

cable, flat media length 375 meters

• 250Kbps @ 200 meters(600 feet) for thick cable,

flat media length 150 meters

• 500Kbps @ 100 meters (330 feet) for thick

cable, flat media length 75 meters

Advertising