Rockwell Automation 1746-NO8V SLC 500 8-Point Analog Output Module/ User Manual User Manual
Page 28

Publication 1746-UM026A-EN-P - September 2003
4-4 Configuring the Module
6. Check boxes and pull-downs allow for complete configuration
for each channel. The pull-downs provide the following
configuration options:
a. The “Channel Enabled” check box controls bit 0 of the
channel configuration word.
b. The “Output Type” pull-down allows configuration of the
output range (bits 1 and 2 of the channel configuration word),
dependent upon the module being used.
1746-NO8I Current Output Type:
0 to 21 mA
4 to 20 mA
0 to 20 mA
1746-NO8V Voltage Output Type:
+10V dc
1 to 5V dc
0 to 5V dc
0 to 10V dc
c. The “Clear Parameter” and “Set Parameter” check boxes
correspond to bits 7 and 8 of the channel configuration word.
A configuration error will occur if both are set.