POINT I/O 2 Current and 2 Voltage Input Analog Modules 15

Publication

1734-IN027A-EN-E - May 2005

Indication

Probable Cause

Module Status

Off

No power applied to device

Green

Device operating normally

Flashing Green

Device needs commissioning due to configuration missing,
incomplete or incorrec.

Flashing Red

Recoverable fault

Red

Unrecoverable fault may require device replacement

Flashing Red/Green

Device is in self-test

Indication

Probable Cause

Network Status

Off

Device is not online
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator

Flashing Green

Device is online but has no connections in the established state

Green

Device online and has connections in the established state

Flashing Red

One or more I/O connections in timed-out state

Red

Critical link failure - failed communication device. Device detected
error that prevents it communicating on the network.

Flashing

Red/Green

Communication faulted device - the device has detected a network
access error and is in communication faulted state. Device has
received and accepted an Identify Communication Faulted Request -
long protocol message.