22 POINT I/O 2 Current and 2 Voltage Input Analog Modules

Publication

1734-IN027A-EN-E - May 2005

General Specifications
(continued)

1734-IE2C

1734-IE2V

ESD Immunity

IEC6100-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to
2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890MHz

EFT/B Immunity

IEC 61000-4-4:
±3kV at 5.0 kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:
±2kV line-earth(CM) on shielded ports

Conducted RF Immunity

IEC61000-4-6:
10Vrms with 1kHz sine-wave 80%AM
from 150kHz to 80 MHz

Enclosure Type Rating

None (open-style)

Wire Size

14 AWG (2.5mm

2

) - 22 AWG (0.25mm

2

) solid or stranded

copper wire rated at 75

o

C or greater

3/64 inch (1.2mm) insulation maximum

Wire Category

2

1 on signal ports

Terminal Base Screw Torque

0.6 Nm (7 lb-in)

Weight

0.035 kg (0.08 lb)