Using the controlnet status indicators – Rockwell Automation 1785-L20C_L40C QUICK START CONTROLNET PLC-5 User Manual
Page 23

4–3
Troubleshoot the Processor System
Publication 1785-10.7 – October 1997
The ControlNet status indicators inform you of the operational state
of the ControlNet network.
Indicator
Color
Description
Probable Cause
Recommended Action
I/O
Off
ControlNet I/O not
present or not
operating
Normal operation if
Channel 2 not being used
No action required
Steady
Green
All nodes configured in
the ControlNet map
table present and
operating properly
Normal operation
No action required
Flashing
Green/Off
At least one node
configured for the
ontrol et net or not
Cable(s) or connector(s)
broken or not connected
Repair or replace cable(s) or
connector(s), and reconnect
reen O
con i ure or t e
ControlNet network not
present or not
o eratin ro erl
Destination module(s) bad
or missing
Repair or replace module(s)
operating properly
Node(s) not on network
Connect node to network
Flashing
Red/Off
All nodes configured
for ControlNet not
re ent or not
Cable(s) or connector(s)
broken or not connected
Repair or replace cable(s) or
connector(s), and reconnect
present or not
operating properly
Nodes not on network
Connect nodes to network
I/O
A
B
Using the ControlNet
Status Indicators