Using the dh+/rio status indicators – Rockwell Automation 1785-L20C_L40C QUICK START CONTROLNET PLC-5 User Manual
Page 25

4–5
Troubleshoot the Processor System
Publication 1785-10.7 – October 1997
Indicator
Color
Channel Mode
Description
Probable Cause
Recommended Action
A or B
Green
(steady)
Remote I/O
Scanner
Active Remote I/O link, all
adapter modules are
present and not faulted
Normal operation
No action required
Remote I/O
Adapter
Communicating with
scanner
DH+
Processor is transmitting or
receiving on DH+ link
Green
(blinking
rapidly or
slowly)
Remote I/O
Scanner
At least one adapter is
faulted or has failed
•
Power off at
remote rack
•
Cable broken
•
Restore power to
the rack
•
Repair cable
DH+
No other nodes on network
Red
(steady)
Remote I/O
Scanner
Remote I/O
Adapter
DH+
Hardware fault
Hardware error
•
Turn power off, then
on.
•
Check that the
software
configurations match
the hardware set-up.
•
Replace the
processor.
Red
(blinking
rapidly or
slowly)
Remote I/O
Scanner
Faulted adapters detected
•
Cable not
connected or
is broken
•
Power off at
remote racks
•
Repair cable
•
Restore power to
racks
DH+
Bad communication on DH+
Duplicate
node detected
Correct station address
Off
Remote I/O
Scanner
Remote I/O
Adapter
DH+
Channel offline
Channel is not
being used
Place channel online if
needed
Using the DH+/RIO