Wire rtd configuration – Rockwell Automation 1790-XXXX CompactBlock LDX I/O DeviceNet RTD and Thermocouple User Manual

Page 11

Advertising
background image

11

Publication 1790-IN011B-EN-P - April 2003

To ensure that the lead values match as closely as
possible:

• keep lead resistance as small as possible and less than

25 ohms

• use quality cable that has a small tolerance impedance

rating

• use a heavy-gauge lead wire which has less resistance

per foot

RTD Wiring Configurations

Three configurations of RTDs can be connected to the
blocks:

• 2-wire RTD, which is composed of an RTD EXC

(excitation) lead wire and a RTN (return) wire

• 3-wire RTD, which is composed of a Sense and 2 RTD

lead wires (RTD EXC and RTN)

• 4-wire RTD, which is composed of a Sense and 2 RTD

lead wires (RTD EXC and RTN). The second sense
wire of a 4-wire RTD is left open.

2-Wire RTD Configuration

CH0_A

CH0_B

COM

Add Jumper

Cable Shield (to Ground)

RTD EXC

RTD EXC

Return

Return