Troubleshoot with the indicators – Rockwell Automation 1790-XXXX CompactBlock LDX I/O DeviceNet RTD and Thermocouple User Manual

Page 17

Advertising
background image

17

Publication 1790-IN011B-EN-P - April 2003

Troubleshoot with the Indicators

The 1790D I/O block has the following indicators:

• module status
• network status
• I/O status

Mod/Net Status Indicator

LED Indicator:

Status:

Description:

Module Status

Solid Red

Unrecoverable fault in base unit

Flashing Red

Recoverable fault

Solid Green

Normal operation - OK

Flashing Green

Standby

Off

No power

LED Indicator:

Status:

Description:

Network Status

Solid Red

Unrecoverable communication fault

Flashing Red

Recoverable communication fault

Solid Green

Communication path complete - OK

Flashing Green

Communication path incomplete

Off

Device not online or not powered

I/O Channel LED Status Indicator

Status:

Description:

Flashing Green/Red

Power up

Off

Off line

Red

On line and no field power

Red

DeviceNet connection and no field power

Flashing Red

Field power and open wire

Green

Field power and valid input

Flashing Red

Input over range

Flashing Red

Input under range

Flashing Red

Recoverable fault

Advertising