Connect Field Wiring

System Wiring Guidelines

Follow these guidelines when wiring your system:

• use shielded, twisted pair wire to ensure proper operation

and high immunity to electrical noise

• to limit noise, locate RTD and resistance device signal wires

as far away as possible from power lines, load lines and
other sources of electrical noise, such as hard-contact
switches, relays and AC motor drives

• under normal conditions, the drain wire and shield junction

should be connected to earth ground, via a panel or DIN rail
mounting screw at the block end

• keep shield connection to ground as short as possible

• to ensure optimum accuracy, limit overall cable impedance

by keeping the cable as short as possible. Locate the I/O
system as close to your field devices as your application will
permit.

RTD Wiring Guidelines

Since the operating principle of the RTD module is
based on the measurement of resistance, give special
consideration when selecting the input cable. For 2-wire
or 3-wire configurations, select a cable that has
consistent impedance throughout its entire length.