ArmorBlock MaXum 8 Output Module Series B 5

Publication 1792D-IN003B-EN-P - September 2000

To install the module:

1. Position the module over the mounted cable base. Align the

three captive screws in the module with the accepting
receptacles in the base.

2. Tighten the screws with a torque of 8 inch-pounds to secure

the module to the base.

IMPORTANT

Proper alignment of the screws is necessary to
complete the connections between the module
contacts and cable contacts.

IMPORTANT

Dimensions change according to the cable base
and module combination used.

42336

1.9in.
48.26mm

6.85in.
174mm

2.7in.
68.6mm

Align the
screws to
properly
assemble
the
module to
the base.

Cable Base
1792D-CBFM is used
for this example.

Assembled
dimensions
in (mm).