Communicate with Your ArmorBlock MaXum
I/O Module

This ArmorBlock module’s I/O is exchanged with the master through
a poll, change-of-state, or cyclic connection.

The module consumes and produces output data as follows:

Cyclic - allows configuration of the block as an I/O client. The block
will produce and consume its I/O cyclically at the rate configured.

Polled - a master initiates communication by sending its polled I/O
message to the module. This 8 output module consumes the
message, updates outputs and produces a response. The response
has output faults and the status of the Auxiliary power.

Change-of-state - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the I/O module is
alive and ready to communicate.

Refer to the table below for the word/bit definitions.

Type of I/O Connections

Consumes

Produces

Cyclic

1 Bytes

2 Bytes

Polled

1 Bytes

2 Bytes

Change-of-State

1 Bytes

2 Bytes

Bit

07

06

05

04

03

02

01

00

Produces 0

OFLT7

OFLT6

OFLT5

OFLT4

OFLT3

OFLT2

OFLT1

OFLT0

Produces 1

RSVP

OPWR

RSVP

RSVP

RSVP

RSVP

RSVP

RSVP

Consumes 0

O7

O6

O5

O4

O3

O2

O1

O0

Where: OFLT = Output Fault OPWR = Output Power O = Output RSVP = Reserved