5. Wire the ControlNet network to the PLC-5 processors and to

the I/O adapters being used for the backup system.

The network cabling may consist of single or redundant channels.

Configuring Your Backup System

Before you begin, make sure that you have installed RSLinx,
RSLogix5 and RSNetWorx. For more details on installing any of this
software, refer to its respective installation documentation.

To configure your backup system, complete all of the following
procedures detailed on pages 4-7:

Initialize the system

Configure handshaking messages with RSNetWorx

Configure I/O

Create and configure the backup integer file

Verify the backup system

Important: These procedures require that both processors are in
the default memory state (i.e., there is no program loaded).

Initialize the System

To begin configuring your backup system, you must first initialize
both processors:

Launch RSLogix 5.

Connect to the first processor.

Clear memory.

Assign a name to your project and save it.

Connect to the second processor, and repeat steps 3 and 4.

Configure Handshaking Messages With RSNetWorx

Use RSNetWorx to set up the send and receive scheduled messages
that allow handshaking between the two ControlNet PLC-5
processors.