Rockwell Automation 1785-CHBM ControlNet Hot Backup Quick Start User Manual

Page 6

Advertising
background image

6

Publication 1785-QS001A-EN-P- - January 2001

3. Set the following:

a. Backup File - This is the 200-word integer data file number

created in RSLogix 5 (e.g. N20).

b. Odd Node Address - enter the node address of the odd node of

the odd/even pair of nodes.

c. Send Message - Enter the message number of the Send Scheduled

Message from the odd node address. (Refer to the number you
recorded earlier.)

d. Receive Message - Enter the message number of the Receive

Scheduled Message from the odd node address. (Refer to the
number you recorded earlier.)

e. Refer to the ControlNet PLC-5 Hot Backup System User Manual

(publication 1785-6.5.24) for other options on how to configure
your backup system. (Other options include
synchronous/asynchronous modes, crossloading, and equivalence
checking.)

4. Repeat these procedures for the other PLC-5 processor.

If your system is properly configured, the primary and
secondary LEDs will not be solid red. Your backup system is
ready.

Verify the Backup System

To verify your system:

1. Place the odd node keyswitch in Run mode.

The Primary LED on the 1785-CHBM cartridge should turn
solid green.

2. Place the even node keyswitch in Run mode.

The QUAL LED on both 1785-CHBM cartridges should turn
solid green. The Secondary LED on the even node should be
solid yellow.

Your ControlNet Hot Backup system is now up and running.