2. Make certain the FlexBus connector (1) is pushed all the way to the left to

connect with the neighboring terminal base/adapter. You cannot install
the module unless the connector is fully extended.

3. Make sure the pins on the bottom of the module are straight so they will

align properly with the connector in the terminal base.

4. Position the module (7) with its alignment bar (6) aligned with the groove

(5) on the terminal base.

5. Press firmly and evenly to seat the module in the terminal base unit. The

module is seated when the latching mechanism (2) is locked into the
module.

Connecting Wiring for the 1794-TB3G, and 1794-TB3GS

Wiring Connections Using 1794-TB3G and 1794-TB3GS

ATTENTION

To reduce susceptibility to noise, power analog modules and
digital modules from separate power supplies. Do not exceed a
length of 3 m (9.8 ft) for DC power cabling.

ATTENTION

Do not daisychain power or ground from this terminal base unit
to any AC or DC digital module terminal base units.

ATTENTION

Do not wire more than two conductors on any single terminal.

Wiring Connections

Encoder
Inputs

Channel 0

Channel 1

24V

Inputs

5V

Inputs

24V Inputs

5V Inputs

A

A-0

B-17

A-8

B-25

A

A-1

B-18

A-9

B-26

B

A-2

B-19

A-10

B-27

B

A-3

B-20

A-11

B-28

Z

A-4

B-21

A-12

B-29

Z

A-5

B-22

A-13

B-30

Outputs

Source Out

Return

O0

A-6

B-23

O1

A-7

B-24

O2

A-14

B-31

O3

A-15

B-32

24V DC

Terminals C-34 and C-50

24V COM

Terminals C-35 and C-51

5 or 24V output power

Terminals C-37 and C-46

-V output power

Terminals C-39 and C-48

Chassis Ground

Terminals B-16, B-33, C-38, C-40…C-45, C-47

ATTENTION

Do not connect 24V signals to the +5V input terminals.
Permanent damage to the module will result.

Input Map

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

0

Channel 0 Current Count (least significant word)

1

Channel 0 Current Count (most significant word)

2

Channel 1 Current Count (least significant word)

3

Channel 1 Current Count (most significant word)

4

Channel 0 Stored/Accumulated Count (least significant word)

5

Channel 0 Stored/Accumulated Count (most significant word)

6

Channel 1 Stored/Accumulated Count (least significant word)

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Chassis
Gnd

Chassis

Gnd

+24V DC COM

COM

Chassis Grounds for Shields

A

B

C

A

A

B

Z

B

Z O0 O1

O2 O3

A

A

B

Z

B

Z

A

A

B

Z

B

Z

A

A

B

Z

B

Z

R0

R1

R2

R3

+V

-V

+V

-V

24V Inputs

5V Inputs

5V Inputs

24V Inputs

A, A = incremental encoder input A (+5 or +24V DC)

B, B = incremental encoder input B (+5 or +24V DC)

Z, Z = incremental encoder input Z (+5 or +24V DC)

O = sourcing outputs

R = returns for sourcing outputs

+V = +5 or +24V DC isolated power externally supplied for outputs (1A max)

+24V DC= 24V DC terminal base power for module

-V = negative isolated power connection (1A max)

COM = return for 24V DC terminal base power for module

Chassis Gnd = chassis ground for input or output cable shields

Input power for Output O0 (A-6); Output O1 (A-7) - C-37 (+) and C-39 (-)

Input power for Output O2 (A-14); Output O3 (A-14) - C-46 (+) and C-48 (-)

NC = No Connection

+24V DC

NC

NC

Chas
GND

Chas