Configuration image, Output map, Configuration map – Rockwell Automation 1794-VHSC Very High Speed Counter Module Installation Instruction User Manual

Page 3: Input map, Counter configuration/mode (configuration word 0), Filter selection (configuration word 1)

Advertising
background image

3

Publication 1794-IN067C-EN-P - January 2012

Configuration Image

When a configuration is sent to the module, it is checked for consistency before
being applied. If an error is found, the PE bit is asserted and the module locally
retains its previous configuration. Your user application program should monitor
the PE bit.

7

Channel 1 Stored/AccumulatedCount (most significant word)

8

PE

FP

NR

TF

OS 3 OS 2 OS 1 OS 0 C1 C0 ZF ZS C1 C0 ZF ZS

Where:PE = Programming error (error code in bits 11:0)

FP = Field power (24V DC power lost)

NR = Not ready (configuring field programmable array FPGA)

TF = Test fail flag = 1 (indicating failure during powerup) red indicator on.

Code in bits 2:0 indicate fail code (1 = RAM; 2 = ROM; 3 = EEPROM; 4 = FPGA)

Test flag = 1 with red indicator blinking, upper byte of counter control word in non-zero

– in production test mode.

OS = Output status (current state of output)

C1, C0 = Stored data count

ZF = Zero frequency detected

ZS = Z input status

Output Map

Dec

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

0

Reserved for test

0 VR1 CP1 CR1 0

VR0 CP0 CR0

1

0

LC3

OE3 FO3 0

LC2 OE2 FO2 0 LC1 OE1 FO1 0

LC0 OE0 FO0

2

Channel 0 PWM Output Value (0-95.00%)

3

Channel 1 PWM Output Value (0-95.00%)

Where:VR = Value reset of stored/accumulated count (channel)

CP = Counter preset (channel)

CR = Counter reset (channel)

LC = Local control (channel) - outputs remain under control when FlexBus is unpowered -

1 = enabled

OE = Output enable (channel) - permitting output to be turned on from FO, compare match

or PWM

- 1 = enabled

FO = Forced output (channel) - 1 = on

PWM = Pulse width modulation (0…9500 decimal)

Configuration Map

Dec

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

0

Counter Configuration

1

Filter Selection

2

Time Base Value/PWM Period

3

Channel 0 Gate Interval

4

Channel 1 Gate Interval

5

Reserved

6

Channel 0 Rollover Value (least significant word)

7

Channel 0 Rollover Value (most significant word)

8

Channel 1 Rollover Value (least significant word)

9

Channel 1 Rollover Value (most significant word)

10

Channel 0 Preset Value (least significant word)

11

Channel 0 Preset Value (most significant word)

12

Channel 1 Preset Value (least significant word)

13

Channel 1 Preset Value (most significant word)

14

Channel 0 Scaler

15

Channel 1 Scaler

16

0

0

0

0

0

0

0

0

S
4

S
3

S
2

S
1

F
4

F
3

F2

F
1

17

0

0

0

0

0

0

0

0

S
4

S
3

S
2

S
1

F
4

F
3

F2

F
1

18

0

0

0

0

0

0

0

0

S
4

S
3

S
2

S
1

F
4

F
3

F2

F
1

19

0

0

0

0

0

0

0

0

S
4

S
3

S
2

S
1

F
4

F
3

F2

F
1

20

First Counter 1st ON Value (least significant word)

21

First Counter 1st ON Value (most significant word)

Input Map

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

22

First Counter 1st OFF Value (least significant word)

23

First Counter 1st OFF Value (most significant word)

24

First Counter 2nd ON Value (least significant word)

25

First Counter 2nd ON Value (most significant word)

26

First Counter 2nd OFF Value (least significant word)

27

First Counter 2nd OFF Value (most significant word)

28

First Counter 3rd ON Value (least significant word)

29

First Counter 3rd ON Value (most significant word)

30

First Counter 3rd OFF Value (least significant word)

31

First Counter 3rd OFF Value (most significant word)

32

First Counter 4th ON Value (least significant word)

33

First Counter 4th ON Value (most significant word)

34

First Counter 4th OFF Value (least significant word)

35

First Counter 4th OFF Value (most significant word)

36

Second Counter 1st ON Value (least significant word)

37

Second Counter 1st ON Value (most significant word)

38

Second Counter 1st OFF Value (least significant word)

39

Second Counter 1st OFF Value (most significant word)

40

Second Counter 2nd ON Value (least significant word)

41

Second Counter 2nd ON Value (most significant word)

42

Second Counter 2nd OFF Value (least significant word)

43

Second Counter 2nd OFF Value (most significant word)

44

Second Counter 3rd ON Value (least significant word)

45

Second Counter 3rd ON Value (most significant word)

46

Second Counter 3rd OFF Value (least significant word)

47

Second Counter 3rd OFF Value (most significant word)

48

Second Counter 4th ON Value (least significant word)

49

Second Counter 4th ON Value (most significant word)

50

Second Counter 4th OFF Value (least significant word)

51

Second Counter 4th OFF Value (most significant word)

52

Counter Control Safe State

53

Output Control Safe State

54

Channel 0 PWM Safe State

55

Channel 1 PWM Safe State

Counter Configuration/Mode (Configuration Word 0)

Bit

7

6

5

4

3

2

1

0

Counter 0

Bit

15

14

13

12

11

10

9

8

Counter 1

Mode

Configuration

Description

0

0

0

0

Counter

0

0

0

1

Encoder X1

0

0

1

0

PWM

0

1

0

0

Encoder X4

0

1

0

1

Period/Rate

0

1

1

0

Continuous/Rate

0

1

1

1

Rate Measurement

0

0

0

Store Count Disabled

0

0

1

Mode 1 – Store/Continue

0

1

0

Mode 2 – Store; Reset/Resume

0

1

1

Mode 3 – Store; Reset/Wait/Start

1

0

0

Mode 4 – Store; Reset/start

110 and 111

Reserved

0

Z input not inverted

1

Z input inverted

Filter Selection (Configuration Word 1)

Bit

7

6

5

4

3

2

1

0

Counter 0

Bit

15

14

13

12

11

10

9

8

Counter 1

Configuration Map

Dec

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Advertising