Specifications – Rockwell Automation 1794-VHSC Very High Speed Counter Module Installation Instruction User Manual

Page 5

Advertising
background image

5

Publication 1794-IN067C-EN-P - January 2012

Specifications

Input Specifications

Attribute

Value

Number of input channels

2

Number of inputs per
counter

2 groups of A/A, B/B, and Z/Z pairs with 5V DC or

15…24V DC terminations

Input voltage

5V DC or 15…24V DC (Determined by terminal base terminations)

Input current

5V DC terminations:

19.1 mA @ 5V DC

25.7 mA @ 6V DC


15…24V DC terminations:

6.1 mA @ 15V DC

10.2 mA @ 24V DC

Voltage, input, off-state

5V DC terminations: <1.25V DC

15…24V DC terminations: <1.8V DC

Current, input, off-state

<0.25 mA

Voltage, input, on-state

5V DC terminations: >2.6V DC

15…24V DC terminations: >12.5V DC

Current, input, on-state

>5 mA

Voltage, on-state, max

5V DC terminations: ±6V

15…24V DC terminations (Refer to Derating Curve)

Input frequency, max

1.0 MHz counter and encoder X1 (no filters)

500 kHz encoder X2 (no filters)

250 kHz endocer X4 (no filters)

Input filter selections

Off, 10

μs, 100μs, 1.0ms, 10.0ms per A/B/Z group

Output Specifications

Attribute

Value

Number of outputs

2 isolated groups of 2:

(0.5A @ 5V DC, max; 1.0A @ 12…24V DC, max)

Output control

Outputs can be tied to 8 compare windows

Voltage range, output supply

5…7V DC; 10…31V DC

Leakage current, off-state

Less than 300

μA

Voltage drop, on-state

5V DC terminations: 0.9V DC @ 0.5 A

12…24V DC terminations: 0.9V DC @ 1.0 A

Current, on-state, max

5V DC terminations: 0.5 A

12…24V DC terminations: 1.0 A

Current per

output pair, max

5V DC terminations: 0.5 A

12…24V DC terminations: 1.0 A

Short circuit current

5V DC terminations: 0.9A

12…24V DC terminations: 4.0A

Outputs are short-circuit protected and turned off until power is
cycled.

Surge current

2A for 50 ms, repeatable every 2 s

Delay TimeOff to On

On to Off

25

μs (load dependent)

150

μs (load dependent)

General Specifications

Attribute

Value

Module location

1794-TB3G and 1794-TB3GS

External DC power supply voltage

Voltage range, nom

Supply voltage

Supply current

24V DC

19.2…31.2V DC (includes 5% AC ripple)

100 mA @ 24V DC

Dimensions, HxWxD (with module
installed on terminal base)

94 x 94 x 69 mm

(3.7 x 3.7 x 2.7 in.)

Isolation voltage

50V (continuous), Basic Insulation Type, between six
isolated areas including:

Flexbus

Module 24V DC power

A0/B0/Z0 inputs

A1/B1/Z1 inputs

00/01 and output power supply 1

02/03 and output power supply 2

Tested @ 850V DC for 1 s

FlexBus current

75 mA @ 5V DC (with terminal base power off)

Power dissipation, max

5.0 W @ 31.2V DC

Thermal dissipation, max

17.1 BTU/hr @ 31.2V DC

Indicators (field side driven, logic side
indication)

1 green/red power/status indicator

6 yellow input status indicators – logic side

4 yellow output tatus indicators – logic side

Keyswitch position

1

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…55 °C (32…131 °F)

Temperature,
nonoperating

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating): 5g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged shock): 30 g

Shock, nonoperating

EC60068-2-27 (Test Ea, Unpackaged shock): 50 g

Emissions

CISPR 11: Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2 kV @ 5 kHz on power ports

±2 kV @ 5 kHz on signal ports

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports

±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

±2 kV line-earth(CM) on shielded ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

Enclosure type rating

None (open-style)

Wire size

Determined by installed terminal base

Wiring category

(1)

2 – on signal ports

2 – on power ports

Terminal base screw
torque

Determined by installed terminal base

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

General Specifications

Attribute

Value

Advertising