1734-ow2 relay sink/source output module, Product code: 0087h, Data map – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual
Page 72: Configuration data, Diagnostic data, Product code: 0087h data map

Publication 1734-UM005B-EN-P - June 2001
B-8 Default Data Maps
1734-OW2 Relay
Sink/Source Output Module
Product Code: 0087h
Data Map:
Output size: 1 bytes; Input size: 0 byte
Configuration Data:
Default: H00 (Default: Fault/Idle value = OFF)
Diagnostic Data
Possible Error Codes:
7
6
5
4
3
2
1
0
)Produces (Rx)
No produced data
Consumes (Tx)
Not used
CH1
state
CH0
state
Where: CH0 = output channel 0, CH1 = output channel 1; 0 = OFF, 1 = ON
7
6
5
4
3
2
1
0
Reserved
IV
IA
FV
FA
Meaning of bits described below
FA = Fault Action
FV = Fault Value
Value
Definition
Value Definition
0
Fault Value
0
OFF
1
Hold Last State
1
ON
IA = Idle Action
IV = Idle Value
Value
Definition
Value Definition
0
Idle Value
0
OFF
1
Hold Last State
1
ON
Code
Error Type
16
Module incorrect or missing. Reported on channel 0, applies to whole module.