1734-ia2 120v ac input module, Product code: 1111h, Data map – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual
Page 79: Configuration data, Diagnostic data, B-15, Product code: 1111h data map
Advertising
Publication 1734-UM005B-EN-P - June 2001
Default Data Maps B-15
1734-IA2 120V ac Input
Module
Product Code: 1111h
Data Map:
Output size: 0 bytes; Input size: 1 byte
Configuration Data:
Filter Values
Default: H00 (1ms)
Diagnostic Data
Possible Error Codes:
7
6
5
4
3
2
1
0
Produces (Rx)
Not used
CH1
state
CH0
state
Consumes (Tx)
No consumed data
Where: CH0 = input channel 0, CH1 = input channel 1; 0 = OFF, 1 = ON
7
6
5
4
3
2
1
0
Reserved
Filter
Meaning of bits described below
Value
Definition
00
1ms
01
0.33ms
10
3ms
11
10ms
Code
Error Type
16
Module incorrect or missing. Reported on channel 0, applies to whole module.