1734-ie2v analog voltage input module, Product code: 0018h, Data map – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual
Page 76: Configuration data, B-12, Product code: 0018h data map

Publication 1734-UM005B-EN-P - June 2001
B-12 Default Data Maps
1734-IE2V Analog Voltage
Input Module
Product Code: 0018h
Data Map:
Output size: 0 Words; Input size: 2 Words
Configuration Data:
7
6
5
4
3
2
1
0
Produces (Rx)
Input Channel 0
Input Channel 1
Consumes (Tx)
No consumed data
7
6
5
4
3
2
1
0
Reserved
DF
AD
R
Notch Filter NF
Engineering Units Low (high byte)
Default value = 06h
Engineering Units Low (low byte) Default value = 66h
Engineering Units High (high byte)
Default value = 3Fh
Engineering Units High (low byte) Default value = FFh
Low Alarm Threshold (high byte) Default value = 0Ch
Low Alarm Threshold (low byte) Default value = 29h
High Alarm Threshold (high byte) Default value =40h
High Alarm Threshold (low byte) Default value = A3h
Meaning of bits described below
NF = Notch Filter Values
Value
Definition
00
50Hz
01
60Hz (default)
10
250Hz
11
500Hz
AD = Alarm Disable
R = Range
Value
Definition
Value
Definition
0
Enable (default)
0
-10 to +10V (default)
1
Disable
1
0 to +10V