SLC 500 Thermocouple/mV Analog Input Module 15

Publication 1746-IN015C-EN-P - July 2001

5. Connect the drain wires to the shield inputs of the terminal block if

appropriate for thermocouple used. See “Wiring Guidelines” on page 10 for
more information.

Channel 0 and 1 drain wires to pin 5

Channel 2 and 3 drain wires to pin 10

Channel 4 and 5 drain wires to pin 15

Channel 6 and 7 drain wires to pin 20

6. Connect the signal wires of each channel to the terminal block.

7. Connect TB1 chassis ground connector to the nearest chassis mounting bolt

with 14 gauge wire. (On the face of the module, TB1 is near the lower part
of the terminal block on the primary side of the PCB.)

8. At the sensor-end of cables from thermocouple/mV devices:

remove the drain wire and foil shield

apply shrink wrap as an option

connect to thermocouple/mV devices keeping the leads short

IMPORTANT

Only after verifying that your connections are correct for
each channel, trim the lengths to keep them short. Avoid
cutting leads too short.

IMPORTANT

If noise persists, try grounding the opposite end of the cable
instead. (Ground one end only.)

TB1

Connect ground wire to TB1 before installing module.