Removing the finger-safe terminal block, Wiring the finger-safe terminal block – Rockwell Automation 1769-IQ16F Compact 24V dc Sink/Source Input Module User Manual

Page 10

Advertising
background image

10 Compact 16-point 24V dc Sink/Source High-speed Input Module

Publication 1769-IN064A-EN-P - April 2003

A removable, write-on label is provided with the module. Remove the label from
the door, mark the identification of each terminal with permanent ink, and slide the
label back into the door. Your markings (ID tag) will be visible when the module
door is closed.

Removing the Finger-Safe Terminal Block

To remove the terminal block, loosen the upper and lower retaining screws. The
terminal block will back away from the module as you remove the screws. When
replacing the terminal block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).

Wiring the Finger-Safe Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.

1. Loosen the terminal screws to be wired.

2. Route the wire under the terminal pressure plate. You can use the bare wire

or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.

TIP

The terminal screws are non-captive. Therefore, it is
possible to use a ring lug [max. 1/4” o.d. with a 0.139”
minimum i.d. (M3.5)] with the module.

wiring the

finger-safe

terminal

upper retaining

lower retaining

Advertising