Input specifications – Rockwell Automation 1769-IQ16F Compact 24V dc Sink/Source Input Module User Manual

Page 14

Advertising
background image

14 Compact 16-point 24V dc Sink/Source High-speed Input Module

Publication 1769-IN064A-EN-P - April 2003

Input Specifications

Specification

1769-IQ16F

Voltage Category

24V dc (sink/source

(1)

)

(1)

Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device.
Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field
device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field
devices connected to the positive side (+V) of the field supply are sourcing field devices. Europe: DC sinking input and
sourcing output module circuits are the commonly used options.

Operating Voltage Range

10 to 30V dc at 30°C (86°F)

10 to 26.4V dc at 60°C (140°F)

Number of Inputs

16

Bus Current Draw (max.)

110 mA at 5V dc (0.55W)

Heat Dissipation

3.55 Total Watts (The Watts per point, plus the minimum Watts, with
all points energized.)

Digital Filter

OFF to ON 0s, 100

µs, 500µs, 1ms, 2ms

ON to OFF 0s, 100

µs, 500µs, 1ms, 2ms

Hardware Delay

OFF to ON 100

µs (typical)

300

µs (maximum)

ON to OFF 250

µs (typical)

1ms (maximum)

Off-State Voltage (max.)

5V dc

Off-State Current (max.)

1.5 mA

On-State Voltage (min.)

10V dc

On-State Current (min.)

2.0 mA

Inrush Current (max.)

250 mA

Nominal Impedance

3K

IEC Input Compatibility

Type 1+

Power Supply Distance Rating

8 (The module may not be more than 8 modules away from the power
supply or controller.)

Input Point to Bus (Compact Bus)
Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec.

75V dc working voltage (IEC Class 2 reinforced insulation)

Isolated Groups

Group 1: inputs 0 to 7

Group 2: inputs 8 to 15

Isolated groups operate in either sink or source configurations.

Input Group to Input Group Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec.

75V dc working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. Code

1

Product Type Code

7

Product Code

69

Advertising