12 Compact 16-point 24V dc Sink/Source High-speed Input Module

Publication 1769-IN064A-EN-P - April 2003

1769-IQ16F Configuration File

The read/writable configuration data file allows the setup of the digital filter settings
for each of the two input groups. Group 0 is inputs 0 - 7, Group 1 is inputs 8 - 15.

The manipulation of the bits from this file is normally done with programming
software (e.g., RSLogix 500, RSNetworx for DeviceNet, etc.) during initial
configuration of the system. In that case, graphical screens are provided via the
programmer to simplify configuration. However, some systems (e.g., 1769-ADN
DeviceNet Adapter) also allow the bits to be altered as part of the control program
using communication rungs. In that case, it is necessary to understand the bit
arrangement.

Spare/Replacement Module Parts

Terminal Block:

1769-RTBN18 (1 per kit)

Door Label:

1769-RL1 (2 per kit)

Door:

1769-RD (2 per kit)

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Filter Time On to Off

Group 1

Filter Time Off to On

Group 1

Filter Time On to Off

Group 0

Filter Time Off to On

Group 0

1

0000000000000000

2

0000000000000000

3

0000000000000000

Filter Time

(1)

(1)

Filter Time:

Word 0, the Filter Time configures

the ON to OFF and OFF to ON hardware delay
times for each input group.

Bit Setting

2.0 msec

0010

1.0 msec

0011

0.5 msec

0100

0.1 msec

0101

0.0 msec

0110

Advertising