Attention – Rockwell Automation 1747-OS302_OS401 SLC 5/03 and 5/04 Processors Firmware/Operating System Upgrade User Manual

Page 3

Advertising
background image

Publication 1747-IN007C-EN-P - October 2002

SLC 5/03™ and SLC 5/04™ Processors Firmware/Operating System Upgrade 3

Figure 1 Component Placement Information

7. Firmly seat the processor back into the chassis.

8. Apply power to the chassis containing the processor while

watching the LED display. All the LEDs should turn on and then
turn off. The download process of the firmware takes up to 2.5
minutes. While the download is in progress, the RUN and FLT
LEDs remain off. The other four LEDs – RS232, DH485 (DH

+ on

the SLC 5/04), FORCE, and BATT – turn on and off in a walking
bit sequence. If the download is successful, these four LEDs
remain on together. If the FLT LED turns on and a combination
of LEDs flash on and off indicating an error condition, refer to
the troubleshooting information on page 4.

9. After completing the download, remove power from the chassis

containing the processor.

10. Remove the processor from the chassis.

11. Carefully remove the firmware upgrade pack and place it in the

anti-static packaging it was shipped in.

Jumper J4

Catalog and Serial
Number Label

The SLC 5/03 and SLC 5/04
processors are

protected from the

firmware download when jumper J4
is in this position:

The SLC 5/03 and SLC 5/04
processors accept the firmware
download when jumper J4 is in this
position:

Mother Board

Daughter Board

OR

SLC 500

CAT

SER

SERIAL NO.

PROC. REV.

UL

SA

PROCESSOR UNIT

MADE IN USA

LISTED IND. CONT. EQ.

FOR HAZ. LOC. A196

CLASS 1, GROUPS A, B, C AND D, DIV. 2

FAC

OPERATING TEMPERATURE CODE T3C

1

3

PROTECT

PROGRAM

J4

OS #

SER

FRN

OPERATING SYSTEM INFO

PLACE FRN UPGRADE LABEL HERE

WHITE

RED

+
-

BATTERY

CURRENT REQUIREMENTS: 1A @ 5 VDC

200mA @ 24 VDC

Place the firmware
upgrade label here.

Firmware
Upgrade/Memory
Module Socket

R

c

ATTENTION

!

Do not remove the processor from the SLC 500
chassis until all power is removed from the SLC
500 power supply.

Advertising