Publication 1747-IN007C-EN-P - October 2002

SLC 5/03™ and SLC 5/04™ Processors Firmware/Operating System Upgrade 5

If the LED’s indicate:

(1)

If the LED’s indicate:

(1)

If the LED’s indicate:

(1)

If the LED’s indicate:

(1)

(1) The DH485 LED on the SLC 5/03 processor is labeled DH+ on the SLC 5/04 processor.

POWER

RUN

FLT

BATT

FORCE

DH485

RS232

Refer to the following key to determine the status of the LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

The Following
Error Exists

Probable Cause

Recommended Action

Fatal Hardware
Error

Major hardware failure due to
noise, improper grounding, or
poor power source.

Cycle power and see if the error
repeats itself. If the error clears,
you should be able to download
the firmware. If the error persists,
contact your Rockwell
Automation representative.

POWER

RUN

FLT

BATT

FORCE

DH485

RS232

The Following
Error Exists

Probable Cause

Recommended Action

Corrupted
Operating
System Memory
Module

The operating system on the
Flash EPROM is corrupt.

Cycle power and see if the error
repeats itself. If the error persists,
either contact your Rockwell
Automation representative for a
new operating system upgrade
cartridge, or download the old
operating system, if available.

POWER

RUN

FLT

BATT

FORCE

DH485

RS232

The Following
Error Exists

Probable Cause

Recommended Action

Flash EPROM
Failure

The processor flash EPROM is
corrupt.

Cycle power and see if the error
repeats itself. If the error clears,
you should be able to download
the firmware. If the error persists,
contact your Rockwell
Automation representative.

POWER

RUN

FLT

BATT

FORCE

DH485

RS232

The Following
Error Exists

Probable Cause

Recommended Action

Corrupt or
Missing
Operating
System

The operating system is missing
or has been corrupted.

Cycle power. If error clears, you
should be able to download the
firmware. If the error persists,
contact your Rockwell
Automation representative for a
new operating system.