Rockwell Automation 1738-AENTR Armorpoint 2 Port Enet Adapter User Manual
Page 13
 
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 13
Publication
1738-IN028B-EN-E - February 2010
Network Status
Status
Description
Recommended action
Off
Device not initialized. Device does 
not have an IP address.
Apply power to device, verify IP 
address, and correct, as needed.
Green
CIP connections present. Device 
online and has an IP address, and CIP 
connections are established.
None.
Flashing 
green
No CIP connections present. Device 
has an IP address, but no CIP 
connections are established.
None.
Flashing 
red/green
Device is in self-test.
None.
Flashing red
One or more CIP connections have 
timed out.
Check for I/O module failure and 
controller operation, and correct, 
as needed.
Red
Duplicate IP address detected.
Verify IP address setting and 
correct, as needed.
System Power
Status
Description
Recommended action
Off
Not active; adapter power is off or 
DC-DC converter problem is present.
1. Verify power is on, and apply 
power if needed.
2. Verify backplane power not 
exceeded, and correct as needed.
3. Replace device.
Green
System power is on; DC-DC 
converter output is active (5V).
None.