14 ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A
Publication
1738-IN028B-EN-E - February 2010
Adapter Power
Status
Description
Recommended action
Off
Not active; adapter power is off.
Apply adapter power.
Green
Power is on; 24V input is present.
None.
PointBus Status
Status
Description
Recommended action
Off
Device is not online.
- Device has not completed 
dup_MAC_id test.
- Device not powered - check 
Adapter Status indicator.
Apply power to device, wait for 
dup_MAC_id to complete, and 
correct, as needed.
Green
Device is online and has connections 
in the established state.
None.
Flashing 
green
Device is online but has no 
connections in the established state. 
Firmware (NVS) update in progress.
None.
Wait for the firmware update to 
complete.
Flashing 
red/green
LED cycle power test present.
None.
Flashing red
Communication faulted device - the 
device has detected a network 
access error and is in communication 
faulted state.
Device has received and accepted an 
Identify Communication Faulted 
Request - long protocol message.
Verify that adapter is properly 
installed, and reinstall, as needed.