Specifications, 4 software features (continued) 2.5 specifications – Rockwell Automation 1771-DB Basic Module User Manual - Series A User Manual

Page 14

Advertising
background image

Isolation

G

The Programming Port is isolated from
the 1771 I/O backplane. (+500 V)

G

The Peripheral Port is isolated from
the 1771 I/O backplane. (+500 V)

G

The Programming Port is isolated from
the Peripheral Port. (+500 V)

Communication Rates

G

300, 600, 1200, 2400, 4800, 9600,
19.2 K bits

G

Communication rates/distances

Wall-clock accuracy

G

Absolute:

v " 5 min/month @ 25

°

C

G

Drift

v " 50 ppm/

°

C

G

Drift

v " 50 ppm/year @ 25

°

C

Port driver and receiver

G

Drive output +3.6 V minimum

G

Receiver sensitivity 200 mV minimum

Math

G

Precision: 8 significant digits

G

Range:

"1E-127 to

"99999999E+127

G

Formats: integer, decimal,
hexadecimal and exponential

Module location

G

One 1771 I/O chassis module slot

Backplane power supply load

G

1.5 A

Environmental Conditions

G

Operational temperature: 0

°

C to 60

°

C

(32

°

F to 140

°

F)

G

Storage temperature: -40

°

C to 85

°

C

(-40

°

F to 185

°

F)

G

Relative humidity: 5% to 95%
(non-condensing)

Keying (top backplane connector)

G

Between 8 and 10

G

Between 32 and 34

G

Formats: integer, decimal,
hexadecimal and exponential

G

Formats: integer, decimal,
hexadecimal and exponential

@@@@ Drive output +3.6 V minimum

@@@@

@@@@

@@@@

Introducing the BASIC Module

Chapter 2

2–4

You can start program execution:

by entering commands at the interactive terminal.

at power-up initialization.

You can store and execute programs in RAM or EPROM. You can store
one user-program in RAM and up to 255 (depending on program size)
independent user-programs simultaneously in EPROM memory.

The programs run single-task mode only. You can generate the following
data types with the BASIC Module:

16-bit binary (4 hex digits)

3-digit, signed, fixed decimal BCD

4-digit, unsigned, fixed decimal BCD

4-digit, signed, octal

6-digit, signed, fixed decimal BCD

3.3 digit, signed, fixed decimal BCD

Refer to Chapter 7, “Data Types” for more information.

Communication

Maximum Distance Allowed

ommunication

Rate (bps)

RS-232-C

RS-423

RS-422

300

50

4000

4000

600

50

3000

4000

1200

50

2500

4000

4800

50

800

4000

9600

50

400

4000

19,200

50

200

4000

2.4
Software Features
(continued)

2.5 Specifications