Diagnostics, Btr word 5 – Rockwell Automation 1794-IJ2XT 2 Input Frequency Module Installation Instructions User Manual

Page 4

Advertising
background image

4

Publication 1794-IN049D-EN-P - January 2009

Status Indicators

When an input indicator (yellow) is lighted, it indicates that a valid signal
(active high or active low) is present at one of the Input terminals.
When wire-off detection is enabled, and a wire-off fault is detected (24 V
DC IEC 1+ input terminal only), a fault indicator (red) is blinked/flashed at
a rate of 1Hz to signal a fault condition. A wire-off fault signal will also be
sent to the backplane. A flashing red fault indication means a valid wire-off
condition for a 24 V DC IEC 1+ Input or a 24 V DC contact switch input
with a shunt resistor.
When an output indicator is yellow, the logic is driving an output alarm
On. After detecting a fault, the internal circuitry will set the output data to
the appropriate safe state, as defined by the module data table. Safe state
control may be adapter dependent. The input and output indicators are on
the field side of the isolation path, and display the logic state of the actual
microcontroller input and output.
The status indicator initially powers up as solid green, indicating the power
supply is operating and internal diagnostic tests are being performed. After
a successful power up test, the indicator remains green. The indicator turns
red in about 1.5 s if there is an internal diagnostics error. The module is
operating correctly when the green OK indicator is on.
A red OK indicator shows that the module is in a Faulted condition
(internal error).

Diagnostics

The frequency input module returns diagnostics to the PLC processor in
word 5 of the BTR file. These diagnostics give you information on the
status or condition of the module.

BTR Word 5

Indicator

Condition

Operating Description

Input (0, 1)

(Freq, or Gate)

Off (Dark)

Input Turned Off, Input Not Used, or Wire Disconnected

On (Yellow)

Input Turned On (Active High or Active Low if Inverted)

Fault (F)

(Freq, or Gate)

Off (Dark)

Wire Connected, Normal Operation or Detection Disabled

On (Red
Flashing)

Wire Disconnected, Fault Condition (for IEC 1+ Proximity switch
or switch contacts with shunt resistor)

Output Alarm

(0, 1)

Off (Dark)

Output Alarm Turned Off

On (Yellow)

Output Alarm Turned On (Logic Drive On)

Status (OK)

Off (Dark)

24V Power Turned Off, or 5V Logic Power Problem

Solid Green

Module OK, Normal Operating Mode

Solid Red

Module Fault, Outputs Disabled

FREQ

GATE

OK

0

FREQUENCY INPUT 2 CHANNEL

1

1794-IJ2

A

llen-Bradley

E

B

F

0

F

FREQ

GATE

1

F

1

F

OUT

0

OUT

1

C

D

A

A = Input indicator.

B = Insertable label for writing individual I/O assignments.

C = Wire-Off Fault indicator.

D = Output indicator.

E = Power/status indicator - indicates power applied to module and status of module.

1794-IJ2 shown

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

word 5

See Table for diagnostics

44760

Input
Word

Bit

Definition

Word 5

Bits

00 - 03

Diagnostic Status - indciates the response from the module; a normal or
non-normal operating condition.

Bit

03

02

01

00

0

0

0

0

0 = Normal Operation (No Failure)

0

0

0

1

1 = Calibration Failure

0

0

1

0

2 = Configuration Failure
A Minimum Frequency Sample Time value other
than 0-9 was selected.

0

0

1

1

3 = Message Failure

0

1

0

0

4 = Lead Break Detection Hardware Failure

0

1

0

1

5 = Major Hardware Failure

0

1

1

0

6 = EEPROM Failure

0

1

1

1

7 = RAM Failure

1

0

0

0

8 = ROM Failure

1

0

0

1

9 = Calculation Failure
The actual Frequency is greater than 32,767 Hz or
3,276.7 Hz (overange). The scaled Frequency is
greater than 32,767 Hz or 3,276.7 Hz (overange).
The % Full Scale calculation (based on Maximum
Frequency) is > 3,276.7%.

1010 - 1111

10 - 15 = Not used

Specifications - Frequency Input Module, Cat. Nos. 1794-IJ2, 1794-IJ2K, and
1794-IJ2XT

Input Specifications

Number of input
channels

2

Number of inputs per
channel

2 - Frequency and Gate (gate used to establish direction)

Input frequency

Maximum - 1-32 kHz w/sine wave; 1-32 kHz w/square wave input

Frequency value

Maximum 32,767 or 3,276.7 (dependent on range)

Input pulse width

20

μs

Resolution/Accuracy

Refer to Resolution/Accuracy table

On-stage voltage, min

10V (24V IEC+1 proximity, encoder input or switch inputs)

On-state voltage, nom
(selected by terminal
base connections)

50 mV AC, 28V AC peak - Extended Magnetic Pickup

500 mV AC, 28V AC peak - Magnetic Pickup

< 3V - Vortex Flowmeter low range

> 6V - Vortex Flowmeter high range

24V DC IEC+1 proximity or encoder input

24V DC Contact Switch input

On-state voltage, max

Limited to isolated 24V DC power supply maximum

On-state current

minimum

nominal

maximum


2.0 mA

9.0 mA

10.0 mA

Off-state current, min

1.5 mA into 24V DC IEC+ terminal

Off-state voltage, max

5.0V DC on 24V DC IEC+1 terminal

Wire-off detection

0.4 mA for proximity, encoder or contact switch with 50 k

Ω shunt resistor

Frequency input
impedance

>5 K

Ω for 50 mV Extended Magnetic Pickup

>5 K

Ω for 500 mV Magnetic Pickup

>10 K

Ω for 3V Vortex Flowmeter low range

>10 K

Ω for 6V Vortex Flowmeter high range

>2.5 K

Ω for 24V DC IEC+1 proximity or encoder input

>2.5 K

Ω for 24V DC Contact Switch input

Gate input impedance

>5 K

Ω for 50 mV Extended Magnetic Pickup

>5 K

Ω for 500 mV Magnetic Pickup

>2.5 K

Ω for 24V DC IEC+1 proximity or encoder input

>2.5 K

Ω for 24V DC Contact Switch input

Output Specifications (meets IEC 1A 24V DC output specifications)

Number of outputs

2 isolated

Output voltage source

Customer supplied

Output voltage

minimum

nominal

maximum


10V DC

24V DC

31.2V DC

Off-state voltage, max

31.2V DC

On-state current

1 mA per output minimum

1.0 A per channel sourced out of module maximum

Current Limited - All outputs can be on simultaneously without derating

Surge current

2 A for 50 ms, repeatable every 2 s

Off-state leakage

Less than 300

μA at 31.2V DC maximum