Rockwell Automation 1794-IJ2XT 2 Input Frequency Module Installation Instructions User Manual

Page 5

Advertising
background image

5

Publication 1794-IN049D-EN-P - January 2009

On-state voltage drop

0.9V DC at 1 A

Output control

Outputs individually assignable to: Frequency, % Full Scale or Acceleration
Alarm

Output switching time

Triggered by frequency alarm or acceleration alarm

Turn on: Less than 0.5 ms

Turn off: Less than 1 ms

General

Module location

Cat. No. 1794-TB3G and -TB3GS Terminal Base Units

External DC power

Voltage range

Supply voltage

Supply current

(Input for +5V logic and 24V DC/DC converters)

19.2…31.2V DC (includes 5% AC ripple)

24V DC nominal

220 mA @ 19.2V DC; 180 mA @ 24V DC; 140 mA @ 31.2V DC

Isolated DC power

Voltage range

Supply voltage

Supply current

Peak AC ripple

(Output to sensors and encoders)

21.6…26.4V DC

24V DC nominal

0-60 mA maximum @ 24V DC (4 devices @ 15 mA = 60 mA)

100 mV maximum

Dimensions (with
module installed in
base)

94H x 94W x 69D mm (3.7H x 3.7W x 2.7D in.)

Isolation voltage

50V (continuous), Basic Insulation Type

Type tested at 1365V AC for 60 s, between field side and system and
individual channels

Processing time

<4 ms

Flexbus current

30 mA at 5V DC

Power dissipation

4.6W maximum at 31.2V DC

Thermal dissipation

Maximum 15.6 BTU/hr at 31.2V DC

Indicators (field side
driven, logic side
indication)

1 green/red power/status indicator

4 yellow status indicators (Freq 0, 1, Gate 0, 1)

4 red wire-off indicators (Freq 0, 1, Gate 0, 1)

2 yellow status indicators (Out 0, Out 1) - logic side

Keyswitch Position

1

Wire size

Determined by installed terminal base

Wiring category

1

2 - on signal ports

3 - on power ports

Wire type

Shielded on signal ports

Terminal screw torque Determined by installed terminal base

Enclosure type rating

None (open-style)

North American temp
code

T4A

IEC temp code

T4

Environmental

Operating temperature IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…55 °C (32…131 °F) (1794-IJ2 and 1794-IJ2K)

-20…70 °C (-4…158 °F) (1794-IJ2XT)

Non-operating
temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Operating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Non-operating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

4 kV contact discharges (1794-IJ2 and 1794-IJ2K)

6 kV contact discharges (1794-IJ2XT)

8 kV air discharges

Radiated RF immunity IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2 kV at 5 kHz on power ports

±2 kV at 5 kHz on shielded signal ports

Surge transient
immunity

IEC 61000-4-5:

±2 kV line-earth(CM) on shielded signal ports

Conducted RF
immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on shielded
signal ports

Certifications

Certifications
(when product is

marked)

2

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL
File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified
for U.S. and Canada. See UL File E194810.

CSA

(1794-IJ2 and
1794-IJ2K)

CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D
Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (II 3 G Ex nA
IIC T4 X)

EN 60079-0; General Requirements (Zone 2)

TÜV

TÜV Certified for Functional Safety:

up to and including SIL 2

1 Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

2 See the Product Certification link at

http://www.ab.com

for Declaration of Conformity, Certificates,

and other certification details.