CompactLogix EtherNet/IP Web Server Module 19

Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

Status Indicators

The module status indicators provides the following information:

Indicator

Status

Description

NET

Off

Module is not powered, or does not have an IP
address.
Verify there is chassis power and the module is

completely inserted into the chassis and backplane.

Make sure the module has been configured.

Flashing Green

Module has obtained an IP address, but has no
established connections.

Green

Module has an IP address and at least one established
connection.

Flashing Red

One or more of the connections in which the module is
the target has timed out.

Red

Module has detected that its IP address is already in
use. Assign a unique IP address to the module.

Link

Off

No data transmission.
Module is not ready to communicate.

Green

Module is ready to communicate.

Flashing Green

Data transmission in progress.
Module is communicating over the network.

OK

Off

Module does not have 5V DC power. Verify there is
power and the module is properly installed.

Flashing Green

Standby mode. Module is not configured.

Green

Module is operating correctly.

Flashing Red

A minor, recoverable fault has been detected. This
could be caused by an error in the configuration.

Red

A major, unrecoverable fault has been detected.
Recycle power to the module. If this does not clear the
fault, replace the module.

Flashing Red and
Green

Module performing power-up self-test.