If You Are Using Screws to Mount Your Modules

The steps in these instructions show how to mount the modules on DIN rail.
If you are using screws instead of DIN rail, make these changes to the
instructions.

1.

Follow the steps in

Mount the Controller on the DIN Rail

on page

10

to

connect the modules together.

2.

Use the modules as a template and mark pilot holes on your panel.

3.

Drill the pilot holes for M4 or #8 screws.

4.

Use M4 or #8 screws to mount the modules to your panel. Use 1.16
N•m (10 lb•in) of torque.

5.

Ground the module on a ground bus with a dedicated earth ground
stake.

6.

Connect the ground bus to a functional earth ground on the DIN rail or
panel.

7.

Refer to Industrial Automation Wiring and Grounding Guidelines,
publication

1770-4.1

, for additional information.

IMPORTANT

Do not use screws and DIN rail to mount the modules. It is
possible to break the mounting tabs off if you screw the modules
to the panel while they are on DIN rail